Customized Three Phase Oil Immersed Transformer
110kV SS11 Series Three-Phase Three-Winding Oil-Immersed Power Transformer
1. Product Overview
The 110kV SS11 series three-phase three-winding oil-immersed power transformer is an energy-saving transmission and transformation equipment developed on the basis of S11 low-loss technology with a three-winding structure.
It is used for power conversion and distribution at multiple voltage levels: 110kV high voltage, 35kV/10kV medium voltage, and 10kV/6kV low voltage.
Meaning of SS11:
First S: Three-phase
Second S: Three-winding
11: Low-loss performance level (no-load loss reduced by ≥30% compared with S9)
110kV: Rated high voltage class
This product complies with national standards GB 1094, GB/T 6451, GB 20052-2020 and international standard IEC 60076.
It is widely used in 110kV substations, regional power supply centers, large industrial parks, metallurgy, chemical industry, new energy collection stations and other multi-voltage power supply scenarios.
2. Model Definition & Structural Features(Customizable)
2.1 Model Definition
SS11–Capacity/110
S: Three-phase oil-immersed
S: Three-winding structure
11: Low-loss level
110: High voltage rated 110kV
2.2 Structural Features
Three-winding structure: HV + MV + LV, capable of outputting 110kV, 35kV, 10kV simultaneously
Three-limb or five-limb core with uniform magnetic circuit
Three-winding capacity can be allocated as 100%/100%/100% or 100%/50%/50%
Fully sealed oil-immersed structure, with corrugated tank or capsule sealing
Suitable for complex power supply systems with multi-power, multi-load and multi-voltage levels
3. Core Technical Parameters
3.1 Rated Capacity
HV winding: 6300~63000kVA
MV winding (35kV/10kV): Equal to HV or proportionally allocated
LV winding (10kV/6kV): Equal to HV or proportionally allocated
3.2 Rated Voltage
HV: 110kV / 115kV / 121kV (±2×2.5% off‑load tap changing)
MV: 35kV or 10kV
LV: 10kV or 6kV
3.3 Connection Group
Standard: YNyn0d11
Optional: YNd11, YNyn0, YNynd11
3.4 Short-Circuit Impedance (Typical)
HV–MV: 10.5%~14%
MV–LV: 6.5%~8%
HV–LV: 10.5%~14%
3.5 Loss Characteristics
No-load loss: ≥30% lower than S9, meets Class 2 energy efficiency
Load loss: Complies with GB/T 6451
No-load current: ≤0.5%
3.6 Insulation Level
Lightning impulse: 450kV (peak)
Power-frequency withstand voltage: 200kV (RMS)
3.7 Cooling Mode
ONAN (Oil Natural Air Natural)
ONAF (Oil Natural Air Forced)
OFAF/ODAF available for large capacity
3.8 Noise Level
ONAN: ≤65dB(A), can be optimized to ≤60dB(A)
3.9 Ambient Conditions
Ambient temperature: -30℃~+45℃
Altitude: ≤1000m (plateau type customizable)
Humidity: ≤95% (at 25℃)
4. Structural & Technological Features
4.1 Core
High-permeability grain-oriented cold-rolled silicon steel (0.27–0.30mm)
Multi-step step-lap joint, hole-free binding
Three-limb or five-limb structure: low magnetic resistance, low vibration, low noise
Phosphating and painting for moisture and rust resistance
Seamless wound core available for lower loss and noise
4.2 Three-Winding Structure
HV: Multi-layer cylindrical type, reliable insulation, high short-circuit strength
MV: Spiral or continuous type, good heat dissipation, uniform current distribution
LV: Foil or spiral type, suitable for heavy current
Oxygen-free copper conductors, low loss, high conductivity
Vacuum drying and impregnation, low partial discharge
End reinforcement for excellent sudden short-circuit withstand capability
4.3 Tank & Sealing
High-quality steel welding, ultrasonic testing, zero leakage
Corrugated tank or capsule sealing, fully sealed against oxidation
Anti-corrosive painting
Oil conservator / capsule for oil volume compensation
Oil-resistant & aging-resistant gaskets
4.4 Insulation System
Composite insulation: pressboard + transformer oil + epoxy parts
Vacuum drying, low moisture content
Partial discharge ≤100pC
Insulation class A (105℃)
4.5 Protection System
Buchholz relay (light alarm, heavy trip)
Pressure relief valve
Oil level gauge
Analog / digital thermometer
Optional: DGA online monitoring, temperature monitoring, automatic fan control
4.6 Cooling System
ONAN: natural convection, energy-saving, low noise
ONAF: automatic fan control, improved overload capacity
Intelligent temperature control: over-temperature alarm, fan linkage
5. Core Advantages
High Efficiency & Energy Saving
No-load loss reduced by ≥30% vs. S9
Significantly lower annual power cost
Ideal for long-term light-load / no-load operation
In line with national “dual carbon” policy
Flexible Three-Winding Structure
Simultaneous multi-voltage output: 110kV, 35kV, 10kV
Suitable for multi-power, multi-load systems
Reduces equipment quantity and investment
Low Noise & Eco-Friendly
Optimized core, noise ≤65dB(A)
Fully sealed, no oil leakage, no volatile pollution
Eco-friendly transformer oil
Excellent Short-Circuit Withstand Capability
High winding rigidity
Stable core and clamping structure
Withstands sudden short-circuit impact
Fully Sealed & Maintenance-Free
Oil isolated from air, stable oil quality
No frequent oil replacement or filtration
Maintenance cost reduced by over 60%
Strong Environmental Adaptability
Resistant to high/low temperature, humidity
Customizable for plateau, anti-corrosion, coastal salt-fog
Outdoor protection IP33
Long Service Life & High Reliability
Design life ≥30 years
High-quality materials & strict manufacturing
Full routine test before delivery
6. Application Scenarios
Power Grid
110kV substations, regional power supply centers, urban distribution network upgrading
Industrial Enterprises
Metallurgy, chemical, mining, cement, large industrial park step-down substations
New Energy Stations
PV power 110kV collection stations, wind farm 110kV boosting stations
Urban Construction
Commercial complexes, rail transit, airports, high-speed rail stations, residential districts
Special Environments
Plateau, cold regions, coastal salt-fog, chemical corrosive environments
7. Installation, Operation & Maintenance
7.1 Installation
Stable, level foundation with good ventilation
Reliable earthing (earthing resistance ≤4Ω)
Standard and firm HV/LV connections
7.2 Operation
Monitor oil temperature, oil level, current, voltage
Avoid long-term overload
Keep radiators clean
7.3 Maintenance
Routine: check oil level, oil condition, appearance
Periodic: oil test, insulation test, partial discharge test
Long-term outage: run fans periodically, inspect insulation