Metal Enclosed Switchgear
KYN28A-12 Switchgear – Key Advantages
Safe & reliable: Full armored compartment design + complete 5-interlock anti-misoperation.
High protection: IP4X enclosure, IP2X with door open, dust & moisture resistant.
Easy maintenance: Central withdrawable circuit breaker trolley, fast replacement.
Flexible application: Modular design for single / sectional / double bus systems.
Strong short-circuit capacity: Up to 50kA breaking, stable under fault conditions.
Compact structure: Space-saving, suitable for indoor distribution rooms.
KYN28A-12 Armored Central Alternating Current Metal-Enclosed Switchgear
1. Product Description
The KYN28A-12 armored central alternating current metal-enclosed switchgear (hereinafter referred to as the switchgear) is a new type of product independently designed by our company on the basis of absorbing advanced manufacturing technology at home and abroad. It can replace various old types of metal-enclosed switchgear, and is suitable for 3.6-12kV three-phase AC 50Hz power grids. It is used for receiving and distributing electric energy, as well as controlling, monitoring and protecting circuits. It can be used for single busbar, single busbar section system or double busbar system.
The switchgear complies with standards including IEC298 Alternating current metal-enclosed switchgear and controlgear for rated voltages above 1kV and up to and including 12kV, IEC694 Common clauses for high-voltage switchgear and controlgear standards, China's GB3906 AC metal-enclosed switchgear for rated voltages of 3.6kV to 40.5kV, DL404 Ordering specifications for indoor AC high-voltage switchgear, and German DIN.VDE0670 AC switchgear for rated voltages above 1kV. It is also equipped with perfect and reliable anti-misoperation functions.
2. Product Model and Implication
Model format: K Y N 28 A - 12 / □□□ - □
| Letter/Number | Supplementary Code (Right) | Implication | |
K | Armored metal-enclosed switchgear | Rated voltage (kV) | Rated voltage |
Y | Withdrawable type | Primary scheme number | Number of primary wiring scheme |
N | Application condition (indoor) | Operating mechanism characteristic code | D: Electromagnetic; T: Spring |
28 | Design serial number | Rated current (A) | Rated current of switchgear |
A | Improved type | Rated short-circuit breaking current (kA) | Short-circuit breaking capacity |
3. Service Environmental Conditions
Ambient air temperature: Upper limit +40℃, lower limit -10℃
Altitude: No more than 1000m
Relative humidity: Daily average relative humidity ≤95%, monthly average relative humidity ≤90%
Seismic intensity: No more than 8 degrees
No fire, explosion hazard, heavy pollution, chemical corrosion and severe vibration at the installation site
If the service conditions exceed the above scope, the user shall negotiate with our company to determine the allowable scope and technical measures
4. Ordering Instructions
The supply scope of 10kV withdrawable switchgear is determined according to the configuration wiring diagram provided by the buyer.
All switchgears are equipped with relays, meters and secondary control equipment in accordance with the secondary wiring drawings provided by the design institute.
The switchgear includes terminal blocks, disconnecting switches and switches connected to the outside, and the secondary wiring inside the cabinet is completely connected in accordance with the secondary wiring diagram.
5. Technical Parameters
| Item | Unit | Data | |
|---|---|---|---|
Rated voltage | kV | 3, 6, 7.2, 12 | |
Rated frequency | Hz | 50 | |
Rated current of circuit breaker | A | 630, 1250, 1600, 2000, 2500, 3150 | |
Rated current of switchgear cabinet | A | 630, 1250, 1600, 2000, 2500, 3150 | |
Rated dynamic stability current (4S) | kA | 16, 20, 25, 31.5, 40, 50 | |
Rated stable current (peak value) | kA | 40, 50, 63, 80, 100, 125 | |
Rated short-circuit breaking current | kA | 16, 20, 25, 31.5, 40, 50 | |
Rated short-circuit making current (peak value) | kA | 40, 50, 63, 80, 100, 125 | |
Rated insulation level | 1min power frequency withstand voltage | kV | 24, 32, 42 |
Lightning impulse withstand voltage | kV | 40, 60, 75 | |
Protection grade | - | IP4X for enclosure, IP2X when isolation compartment and circuit breaker compartment door is opened |